Transient multi-loop analysis on the stator ground fault of large synchronous generator--Experimental verification

张琦雪,王祥珩,毕大强
DOI: https://doi.org/10.3321/j.issn:1000-0054.2003.09.002
2003-01-01
Abstract:Stator ground faults of large synchronous generators were analyzed with a transient model based on the multi-loop method. This model partitions the stator windings into many unit circuits and considers the distributed capacitances of the stator windings to the ground as quasi-distributed capacitances. The simulations were compared with experimental results for a ground fault in the stator windings of a 12 kW synchronous test generator as a single machine with no load and neutral grounding with a resistor. The simulation results for the voltages of the three-phases terminals and the neutral were within 7.0% of the experimentally measured voltages. The transient multi-loop model, therefore, provides an excellent way stator ground faults.