A De-excitation Study of Synchronous Generator at Fault

Chen Xianming,Wang wei,Lv Hongshui,Wang Tong,Liu Guohua
DOI: https://doi.org/10.3969/j.issn.1673-3800.2007.03.019
IF: 1.63
2007-01-01
Electrical Engineering
Abstract:The paper describes study results of de-excitation of synchronous generator at fault with three conventional de-excitation methods.In considering the effect of damping winding,Park equations in d,q axis are used.Specially,no-load characteristic(NLC) of generator is represented by analysis expression,so the effect of saturation of NLC on de-excitation is included.Differential equation group is successfully solved with integrators in Simulink simulation.Finally,an example of de-excitation of a Three-Gorge 700Mw synchronous generator at fault on no-load with three de-excitation methods is given.
What problem does this paper attempt to address?