An Application Study of a New De-Excitation Method for Generator with Self-Shunt Excitation

Chen Xianming,Wang Wei,Lv Hongshui,Liu Guohua,Zhu Xiaodong
DOI: https://doi.org/10.3969/j.issn.1673-3800.2007.08.013
IF: 1.63
2007-01-01
Electrical Engineering
Abstract:A new de-excitation method, in which capacitors with parallel connected varistor are connected to both terminals of field winding described in literature[1]. It utilizes resonance produced between capacitors and field winding, soon after field breaker opening. The resonance causes voltage rise of the capacitors . Varistor will put into operation when voltage of the capacitors rises higher than threshold value of the varistor Then voltage of the capacitors no long rises. Requirement for arc voltage of field breaker opening in this case is decreased. In the paper, with the new de-excitation method, de-excitation a self-shunt excited no-load generator after mal-forced excitation is studied. Park equations in d,q axis of synchronous generator with damping winding in rotor are used. Besides influence of saturation of no-load characteristic of generator is accounted. Finally an example simulation is implemented and the predicted results are obtained.
What problem does this paper attempt to address?