Discussion on De-excitation with Serially Connected Varistors

CHEN Xianming,Lü Hongshui,LIU Guohua,WANG Wei,ZHU Xiaodong
DOI: https://doi.org/10.3969/j.issn.1671-3893.2007.06.005
2007-01-01
Abstract:Usually,varistors are adopted in de-excitation(DE)of large generators.Conventionally,varistors are connected parallel to field winding.However,in the operation of larger hydraulic generators,such as Three Gorges 700 MW generators,the magnetic field current and voltage are very large.In order to put into action varistors in parallel connection,the requirements for opening arc voltage(OAV)of field breakers are high.That means not only huge rated current,but also high OAV needed for field breakers.That is the reason of large size,complex structure,high price and difficult maintenance of breakers.The paper proposes that varistors be connected across to both terminals of field breakers.This means that varistors are serially connected in the field circuit during DE and OAV of breakers can be reduced to the threshold voltage of the varistors.Such a way has the same effect on DE as the conventional method without additional equipment.The paper describes the simulation results of DE with serially connected varistors of the generator with self-shunt excitation and mal-forced excitation.The proposed method is proved available.