Principles of Vibration Spark Discharge in Stator Slots of Large Generators

XIA Yinglai,JIA Zhidong,ZHANG Zhengping,CHEN Hai,GUAN Zhicheng,WANG Liming
DOI: https://doi.org/10.3969/j.issn.1003-6520.2013.04.035
2013-01-01
Abstract:The damage brought by vibration spark discharge in high voltage stator slots of large generators is severer than that by partial discharge.Therefore,we studied the cause and necessary conditions of spark vibration spark discharge.Firstly,principles of vibration spark discharge were studied based on a capacitive model and a main magnetic model.Meanwhile,the induction voltage and ground current of the corona layer at the middle and end sections of a bar were calculated and verified through experiments.Thereby,the reason why the vibration spark discharge emerged was clarified.Secondly,a model platform of vibration spark discharge in stator slots was established,by which the induction voltage and the ground current that influenced the emergence of the discharge were studied,namely,the voltage-current(VI) characteristics of the discharge.Finally,the optimal resistivity of corona layer,which could resist the discharge in stator slots,was calculated based on the theoretical analysis and experimental results.For example,for large generators rated at 600 MW,the suggested surface resistivity of corona layer is 7.2~18.9 kΩ.
What problem does this paper attempt to address?