Improved VSG Control Strategy for Wind Turbines Connected to Non-Synchronized Grid under Commutation Failure

Xiao Jin,Heng Nian,Chen Zhao,Zhuan Zhou
DOI: https://doi.org/10.1109/cieec54735.2022.9846709
2022-01-01
Abstract:The non-synchronized grid refers to a 100% renewable energy power system without synchronous generators. The wind turbines connected to the non-synchronized grid adopt virtual synchronous generator (VSG) control strategy to provide virtual inertia of power system. Commutation failure is a typical failure of the non-synchronized grid to send renewable energy through the ultra-high voltage (UHV) dc transmission system. The commutation failure can cause severe overvoltage on the non-synchronized sending terminal AC grid. The transient current characteristics of wind turbines adopting VSG control under commutation failure are analyzed. An improved VSG control strategy is proposed to suppress the overvoltage of the sending terminal grid under commutation failure. The effectiveness of the improved VSG control strategy is verified by a simulation model of wind turbines connected to an UHV dc transmission system based on Matlab/Simulink. In addition, the simulation model also verifies that the proposed strategy can reduce the overcurrent of the wind turbine under commutation failure.