Analysis And Improvement On Stator Earth-Fault Protection By Injecting 20hz Signal

Dq Bi,Xg Wang,Zy Xu,Wj Wang
2001-01-01
Abstract:By analyzing the sensitivity and its influencing factors of stator earth-fault protection by injecting 20Hz signal, this paper puts forward an improved protection scheme based on the impedance angle and its mutation component. The simulation results verify this kind of protection scheme has higher reliability and sensitivity under the generator neutral grounding through distribution transformer with secondary resistor and arc-extinguishing coil comparing with the conventional criterion. Against different grounding modes the sensitivity of protection scheme is further improved by correspondingly adjusting the frequency of injecting signal.