Study on Voltage-Type Longitudinal Zero-Sequence Inter-Turn Protection for Generator

Min YANG,Xi-dong XU
DOI: https://doi.org/10.3969/j.issn.1674-3415.2007.16.003
2007-01-01
Abstract:This paper details how the inter-turn protestions of the generator is actuated due to a grounding failure outside the primary power area,introduces the operation theories of the protections and the ways to calculate and set the ratings. It focuses on performing research on the variation discipline of the basic wave and the third harmonci component in the longitudinal zero-sequence voltage under condition of grounding failure outside the area through analysis of the actual operation conditions and on the basis of the failure waveform recorder data. It points out the theory that supports to use the variation of the stator windings’ third harnomin wave to brake the variation of the basic wave needs further discussion in accordance with the theories and rating settings of the protections,analyzes some problems existing currently in the protections,works out the negative-sequence power variation curve before and after the occurrence of grounding failure outside the area and finally presents some suggestion about improvement of the stator inter-turn protections.