Discussion on Setting Calculation of Loss-of-excitation Protection for Large Turbogenerator

Yao Siwang,Wang Weijian,Luo Ling,Gui Lin
2010-01-01
Abstract:Loss of excitation (LOE) is a common fault found in the generators. The most widely applied method for detecting a generator loss of excitation is the use of impedance relays to sense the variation of impedance as viewed from the generator terminals. However, compared with China's approachs, in the setting of impedance circle, the IEEE's allow the circle to extend along the negative X axis, meanwhile, in the latest edition of the "IEEE Guide for AC Generator Protection", the circle is further extended, reaching to -1.25Xd. We think this is adverse, to prove our point, the paper, basing on the IEEE 9 bus model and using computer digital simulation, have studied various loss-of-excitation conditions and some system disturbances that may lead to the relay false tripping. Simulation results indicate that the IEEE's method not only can't accelerate the operation effectively, but also will increase the chances of maloperation.