Discussion on setting calculation of generator loss-of-excitation protection:thinking of IEEE Guide for AC Generator Protection published in 2007
WANG Weijian,GUI Lin,WANG Lei,WANG Liqun,TANG Yunan
DOI: https://doi.org/10.3969/j.issn.1006-6047.2009.03.001
2009-01-01
Abstract:Opinions different from the setting calculation of loss-of-excitation protection in IEEE Std C37.102TM-2007 IEEE Guide for AC Generator Protection are proposed. It is clearly and definitely pointed out that:when loss-of-excitation occurs,there must be slip,the average asynchronous impedance Xd(js) is much smaller than Xd(s=0),while the lower setting of impedance element is-Xd,which is far enough,-(1.1~1.25)Xd is not necessary; in the coordinates transformation formula between P-Q and R-X,the voltage U should be set according as the principle of "loss-of-excitation protection operates later than UEL (Under Excitation Limiter)" ,not to select 0.95 UN subjectively.