Hidden Defect of Transformer Differential Protection

XU Xi-dong,LUO Zheng,FANG Yu-dong
DOI: https://doi.org/10.3321/j.issn:1000-1026.2005.13.019
2005-01-01
Abstract:With the increase of power system capacity, zero-sequence current caused by earth fault increases. However, traditional transformer differential protection does not take the current transformer error into account to eliminate the zero-sequence current and hence the possibility of mal-operation exists. This paper analyzes the distribution and magnitude of fault current as well as the through current and the differential current in the protection when external earth fault occurs at source side of the transformer. The hidden defect of traditional differential protection is picked out. The countermeasure of zero-sequence current restraint is presented to eliminate this hidden defect.