Sensitivity shift of the transformer longitudinal differential protection due to adjusting the transformer on-load tap changer

CHEN Zhi-feng,XU Xi-dong,XU Liang
DOI: https://doi.org/10.3969/j.issn.1674-3415.2006.13.001
2006-01-01
Abstract:Transformer longitudinal differential protection can discriminate the internal resistance ground fault and the turn-to-turn fault,but the protective sensitivity is low.This paper analyses the vector of the unbalanced differential current caused by adjusting the transformer on-load tap changer(OLTC) and the vector of differential current caused by internal resistance ground fault.It points out that moving up or down the OLTC will increase the unbalanced differential current,but they have different influence on the sensitivity.Finally,an example is given to show the different influence.