Influence of Balance Coefficients of Transformer Differential Protection on Setting of Differential Current Shreshold

XU Xi-dong,ZENG Ping,FANG Yu-dong
DOI: https://doi.org/10.3969/j.issn.1001-9529.2006.08.026
2006-01-01
Abstract:Different from traditional protections using balance winding,the digital transformer differential protection uses balance coefficients.In the balance coefficient setting,the selection of reference side of the transformer exerts direct influence on the setting of the minimum operating current(differential current threshold) of the differential protection.Four methods for selecting the reference side are discussed,and the corresponding relation between setting of the differential current threshold and the reference side is proposed to make a better setting of the differential current threshold for various protection devices.