Effect of progressive short-circuit fault on transformer differential protection

徐习东,董立,颜伟林
DOI: https://doi.org/10.3969/j.issn.1001-9529.2003.10.008
2003-01-01
Abstract:A model of trigonometric function with the amplitude increasing with the time was proposed to simulate the progressive fault current in a transformer progressive short circuit failure.The change rules of the secondary harmonics and dead angle of the fault current waveform under various fault developing rates were analyzed and the effect of the fault current on two kinds of transformer relay protection of different principles was obtained,which will provide a correct concept on analysis of the mistrip of differential protection during a progressive failure in the transformer.
What problem does this paper attempt to address?