Research on Short-Circuit Vibration of Power Transformer

洪凯星,潘再平,黄海
DOI: https://doi.org/10.3969/j.issn.1001-4551.2010.06.021
2010-01-01
Abstract:Diagnose transformer using vibration method is a new trend which can monitor without shut apparatus down,but this method is still unsatisfied.The vibration signals from the transformer tank are complicated,and it is important to find a model which can reflect the vibration correctly.Aiming at how to simplify the vibration model,a transformer tank vibration model under short-circuit condition was presented.The model was based on how signal generates and how signal transmits.The model was obtained using data set sampled in single phase short-circuit tests.With the fully trained model,the estimated vibration signal at one point was calculated by employing the input current only.In order to validate the model,three phase short-circuit tests were taken.The results show a good agreement between estimated signals and measured signals,the results indicate that it is feasible to use a simplified windings and transmission model.
What problem does this paper attempt to address?