Steady-state Analysis of Internal Short Circuits of Multi-winding Power Transformer Part Ⅱ Experiment Verification and Sensitivity Analysis of Differential Relay Protection

TANG Qichao,WANG Zanji,WANG Weijian
DOI: https://doi.org/10.3321/j.issn:1000-1026.2006.11.008
2006-01-01
Abstract:An experiment has been carried out by locating various short circuits one by one in the windings and measuring the voltages and currents at line ends of a three-phase double-winding power transformer. The comparisons between measured results and calculated ones verify the proposed equivalent circuit model and the calculation method in reference [1] for simulating internal short circuits in power transformers. Based on the verification of the simulation method, the sensitivity of the existing differential relay protection has been analyzed using calculated results of the internal short circuits to ground, inter-turn short circuits and inter-phase short circuits for the testing transformer and the conclusion has been made that the sensitivity of longitudinal differential relay protection is satisfactory for the transformer and the further study is needed to improve the sensitivity of neutral current differential relay protection.