Effects of Internal Short Circuit Faults on Short Circuit Reactance of Power Transformer

WANG Zan-ji,TANG Qi-chao,LIU Xiu-cheng
2006-01-01
Abstract:Based on the method of calculating short circuit reactance in transformer design, a study on effects of internal short circuit faults on the short circuit reactance has been carried out. The results show that the internal short circuit causes the unbalanced axial distribution of ampere-turns and increase the transverse leakage magnetic field (TLMF) component. The existence of TLMF will increase the leakage inductance. However, when the internal shirt circuit happens in the primary winding, the contribution of decreasing leakage inductance owing to decrease of the total ampere-turns is more considerable than the contribution of increasing leakage inductance owing to increase of TLMF and hence, the short circuit reactance decreases. When the internal shirt circuit happens in the secondary winding whose terminals are connected together, the short circuit reactance at primary side may increases. No matter where the short circuit happens, the reactance is not equal to rating one and its value increases or decreases nonlinearly with the change of the fault position.