AN INDUCTANCE CALCULATION MODEL OF POWER TRANSFORMER FOR INTERNAL FAULT ANALYSIS

王赞基,刘秀成,陈香辉
DOI: https://doi.org/10.3321/j.issn:1000-1026.2000.24.007
2000-01-01
Abstract:For the purpose of precious internal fault analysis and relay protection of the power transformer, some problems in the existing models are pointed out. The key problem is that the difference of the leakage magnetic field distribution between normal operation and fault condition has not been taken into account. Therefore, the original short circuit reactance or leakage inductance of the transformer can't be used to develop the model parameters of the faulty transformer. This paper presents a new method to determine the leakage inductance of a power transformer. Based on the principle of linear superposition of the leakage magnetic field, the leakage inductance of the faulty transformer is firstly calculated on the basis of the geometric dimensions of the windings by subdividing windings into several sections according to the fault location. Then, the obtained inductance matrix will be modified according to the concept that the sum of the ampere-turns of all harmonics in the transformer windings is equal to zero. The application of the proposed method has shown that the method has the flexibility and sufficient precision in the internal fault analysis.