Analysis of the Maloperation of Transformer Differential Protection after External Fault Removed

Xiao-yu ZHANG,Da-qiang BI,Peng-sheng SU
DOI: https://doi.org/10.3969/j.issn.1674-3415.2006.01.002
2006-01-01
Abstract:After an external fault of transformer is cleared,the transient flux may enter into the saturation region,and a recovery inrush may be produced.At the same time,the aperiodic component in the fault current usually has a high value during the fault,so that the CT may also enter into the saturation region.Both of them may cause the maloperation of the differential protection.In this paper,the flux of the transformer is obtained by theoretical derivation,then models of transformer and CT are built for simulation,and an experiment is done to prove the results.The factors that affect the inrush are analyzed.The influence on the inrush of the differential protection is investigated and the saturation of CT is studied as well.At last,considering the inrush and the saturation of CT together,the main cause of the maloperation is discussed.