Necessity of Zero-Sequence Differential Protection for Large-Sized Transformer

王维俭
DOI: https://doi.org/10.3969/j.issn.1006-6047.2003.04.001
2003-01-01
Abstract:The statistical material of operation shows that,most of transformer’s winding faults is the inter-turn short-circuit,the next one is the grounding fault,and the least is the inter-phase short-circuit.When the single-phase grounding fault occurs in the Y N winding of transformer,the phases of bilateral currents of longitudinal differential protection may be same ,which is the phase characteristic of the external short-circuit.Therefore,the sensitivity of longitudinal differential protec-tion is reduced.To simplify the phase analysis between currents in the transformer fault analysis and the performance anaysis of differential protection,the reference direction of primary an d secondary currents should be defined in terms of subtractive polarity method and the phase current shoul d be directly analyzed by the per-unit system,rather than the classical symmetrical component method.