Using the sampling differential protection based on the constructed restraint current to identify CT saturation

YANG Hui-hong,XIE Bai-huang,BI Da-qiang,ZHANG Xiang-an,WANG Wei-jian
DOI: https://doi.org/10.3969/j.issn.1674-3415.2006.13.013
2006-01-01
Abstract:This paper analyzes the mechanism which caused CT saturation and the essential character of the current secondary side at CT saturation.According to the linear zone of secondary current of CT near the primary current across zero,a method is proposed to identify CT saturation by using the sampling differential protection based on the constructed restraint current. The theoretical analysis and experiments verify that the method can prevent the differential protection from mal-operating while the CT enters into saturation caused by the external fault.The reliability of differential protection is improved,and the method has been applied in the practice.