Effects of Neutral Earthing on the Occurrence of Sympathetic Inrush in Transformer

Da-qiang BI,Ye SUN,De-jia LI,Xiang-heng WANG,Wei-jian WANG
DOI: https://doi.org/10.3969/j.issn.1674-3415.2007.20.002
2007-01-01
Abstract:The sympathetic inrush is harmful to the operation of transformer. At present, it is well believed that cutting the passage of inrush is an effective way to avoid the occurrence of sympathetic inrush in transformer by opening the grounding switch at the neutral of operating transformer or energizing transformer. By the numerical simulation and the experiment to analyze the effect of neutral earthing on the occurrence of sympathetic, this paper verifies that whether the neutral of operating transformer or energizing transformer earthing or not, the sympathetic inrush may occur in operating transformer when a transformer energized in parallel or in series. Changing the situation of neutral earthing, the sympathetic inrush will be variable. It is pointed that opening the switch of neutral earthing cannot get rid of the sympathetic inrush and prevent the differential protection to mal-operate, which means that the neutral earthing is not necessary condition for the occurrence of sympathetic inrush in transformer. This project is supported by National Natural Science Foundation of China (No. 50507014) and Electrical Power Science and Technology Foundation of Xuji.
What problem does this paper attempt to address?