Fault location method for eliminating the influence of the mutual inductance of transmission lines in common corridor using one-terminal data

WANG Bo,Xidong Xu,YuDong Fang
DOI: https://doi.org/10.3969/j.issn.1674-3415.2011.14.001
2011-01-01
Abstract:Based on lumped parameter model,an one-terminal fault location method for transmission lines in hybrid corridor with single circuit line is presented.The proposed algorithm uses cascade voltage source on faulty line as an equivalent of the influence of mutual inductance of adjacent lines.Then the superimposed system is dismounted using the superposition theorem.According to the analysis of the complex sequence networks,the relationship among sequence-currents in each system and the relationship between measured current and fault point current are derived.Combining with the solution formula of the sequence current on the fault point,the fault location equation eliminating the influence of mutual inductance of adjacent lines is derived.This method uses one-terminal data and eliminates the influence of transition resistance.Simulation results show that the proposed fault location method has a satisfactory precision.