Experimental Investigation on Surface Conditions of Conductors in AC Power Transmission Lines
BIAN Xing-ming,YANG Wen-yan,ZHAO Lei,WANG Li-ming,GUAN Zhi-cheng
DOI: https://doi.org/10.13336/j.1003-6520.hve.2011.01.014
2011-01-01
Abstract:The influence of conductor surface conditions on corona discharge is of great value to the design and operation of power transmission lines in power system.Six strands of the aged conductors acquired from 500 kV AC transmission lines in northern,central,southern China respectively and two strands of the new conductors China were used.The results of scanning electron microscopy(SEM) and energy-dispersive X-ray analysis(EDX) showed that the morphologies of the aged strands were greatly different from the new ones.The aged strands had been corrupted in the ambient atmospheric conditions during their long-term operating in power grid;many substances in the neighborhood of the conductors were also adhered to the surfaces as a result of the strong electric field and gravitational force.Therefore,the surfaces of the aged strands are much coarser and more uneven than the new ones.For the new strands,aluminum is the main component,there are few impurities.However,in the surface layer of the aged strands,there are many other elements,such as oxygen,carbon,silicon,sulfur,chlorine,kalium,calcium,zincum,natrium,iron,magnesium etc.Two basic roughness parameters Ra and Rq were introduced to express the roughness degree of the strands.Ra and Rq of the aged strands was much more than the new ones.The roughness degree of the strands was similar in the same area,and it increased as the operating time became longer.