Simulative Calculation of UHV Line Secondary Arc Current

陈剑萍,张思,丘文千,戴攀,陈光,王东举,周浩
DOI: https://doi.org/10.3969/j.issn.1006-6047.2009.04.016
2009-01-01
Abstract:The model of 1 000 kV transmission line with two sources is established,based on which the se-condary arc currents are calculated with EMTP for that with and without the HSGS(High Speed Grounding Switch) or the SRNR(Shunt Reactor with Neutral Reactance).It shows that,the SRNR is better for the secondary arc current suppression.The influences of the transient grounding resistance and the line carrying capacity on the secondary arc current are discussed.Results show that,only the transient grounding resis-tance influences obviously the secondary arc current of line with HSGS,the bigger the resistance is,the smaller the arc current will be.The analysis shows that,for the UHV line,it is more reasonable to set the HSGS grounding resistance at less than 1.5 Ω and both the secondary arc current and recovery voltage are minimal when the shunt reactor is set at 150 Ω.Simulations are carried out for long and short lines separately,which shows that,the longer the line is,the bigger the secondary arc current will be.