Simulation on Transient Characteristics of Medium Voltage DC Distribution System

T. Zhu,Z. Q. Yu,R. Zeng,G. Lyu,Z. Y. Chen,X. Y. Zhang
DOI: https://doi.org/10.1049/cp.2016.0420
2016-01-01
Abstract:This paper has focused on the ±10 kV/1 kA medium voltage DC distribution system simulation and analysis. Firstly, parameters and the topology of the middle-voltage DC system simulation model is proposed. Then, with the application of DC circuit breaker, the interpoles fault transient situations of DC system are analyzed in PSCAD/EMTDC. Finally, the influence of various system parameters is discussed. The results show that system parameters have a greater impact on changes in fault transient voltage and current. And DC circuit breaker will limit the peak of fault current immediately. It will be a valuable reference for the system parameters settings and equipment selection.
What problem does this paper attempt to address?