Simulation of Line Protection of HVDC Transmission Based on PSCAD/EMTDC

Zhu Yu,Liang Xu,Min Yong
DOI: https://doi.org/10.3969/j.issn.1007-2322.2006.02.008
2006-01-01
Abstract:This paper develops the practical traveling wave protection system of HVDC transmission lines based on PSCAD/EMTDC.The paper analyzes the fault characteristics of HVDC transmission lines.Upon the theory of traveling wave,the value and direction of the transient current and voltage due to the short circuit fault happened in the DC line will not be affected by the control system of HVDC.So the short circuit fault of the DC line can be detected by calculating the decline rate of direct voltage and comparing the setting values with the transient traveling wave of DC current and voltage after the fault.The traveling wave protection model of HVDC transmission lines is applied into the simulation model of the Gui-Guang HVDC transmission in the South Grid of China with a grounded fault near the rectifier of the transmission line in pole 1.The simulation result proves that the proposed traveling wave protection system of HVDC transmission lines is correct and can be applied into the real HVDC transmission system.
What problem does this paper attempt to address?