Identification of Permanent Faults for Three-Phase Adaptive Reclosure Based on Waveform Characteristics of Differential Mode Currents in Shunt Reactors
WANG Qingqing,WANG Huifang,LIN Da,HE Benteng
DOI: https://doi.org/10.13335/j.1000-3673.pst.2015.04.038
2015-01-01
Abstract:When two-phase temporary or permanent fault or three-phase temporary or permanent fault occurred in UHVAC transmission line with shunt reactor, the characteristics of differential mode current of shunt reactor in fault phase is analyzed in detail. After the three-phase tripping out at both ends of the transmission line, for temporary fault since the arc blowout at the fault point there is only the decaying periodic component in the differential mode current of shunt reactor, and for permanent fault there is only decaying DC component in the differential mode current of shunt reactor. Utilizing such a characteristic of the differential mode current of shunt reactor, it is possible to propose a new criterion that only suits to the identification of phase-to-phase fault characteristic during the three-phase adaptive reclosure, and this criterion can be realized by using the current in the shunt reactor current at one end and the moment of arc blowout can be judged as well. A lot of ATP/EMTP based simulation results show that using the proposed method the fault type can be distinguished rapidly and accurately, and basically the recognition is not affected by such factors as fault position, transition resistance, sampling frequency, load current, the moment when the fault occurred, the moment when the circuit breaker tripped out, and the moment of arc blowout at the fault point, besides, the proposed method is suitable for the transmission lines connected with shunt reactors at single end or both ends.