FAULT LINE SELECTION IN THE NON-SOLID EARTHED NETWORK BASED ON THE MODEL IDENTIFICATION METHOD

索南加乐,张超,王树刚
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.19.014
2004-01-01
Abstract:On account of the weak fault current and unstable fault arc, the problems of the single phase to ground fault line selection in the non-solid earthed network have never been thoroughly resolved. A new line selecting method based on identifying the parameters of the line models is presented in this paper. The mathematical model for each line built under the condition of earth grounding fault beyond the line can be solved with the zero sequence voltage and current. Based on the grounded capacitance of the line obtained, a judgment can be made on whether the fault style accords with the actual one, thus further identifying the fault line. This principle was verified with an EMTP simulator and the field data recorded. The results show that this method, which is free from the impact of arc-suppression coil and unstable arc, has higher sensitivity and reliability. In particular, it can be combined with the feeder protection to meet the requirement for automation.
What problem does this paper attempt to address?