New accurate fault location algorithm for series compensated lines using synchronous data

Chen Zheng,Dong Xinzhou,Luo Chengmu
2002-01-01
Abstract:This paper presented a new synchronized sampling two-terminal fault location algorithm for series compensated lines. In the algorithm, transmission line and metal oxide varistors (MOVs) are approximated by distributed parameters modal and multi-exponential modal separately, and the instantaneous values of the voltage drop across MOVs is estimated with Newton iterative method. Two computing steps, the step of fault behind series capacitors and the step in the front of series capacitors, are used in the proposed algorithm to calculate the real fault distance. The accuracy of the fault location algorithm is extensively tested using the EMTP generated data with respect to the modal .of a 500kV 300km transmission line under different fault location, fault resistance and fault inception angel. The enclosed simulation results demonstrate this new algorithm has high accuracy, and the location error is less than 0.5% for all cases.