A Time-domain Fault Location Algorithm Based on One-terminal Current of Parallel Transmission Lines

SUONAN Jia-le,SONG Guo-bing,KANG Xiao-ning,WANG Shu-gang
DOI: https://doi.org/10.3321/j.issn:0258-8013.2007.07.010
2007-01-01
Abstract:A novel fault location algorithm for parallel transmission lines by one-terminal current is presented. Parallel transmission lines can be uncoupled into Common Component Net and Differential Component Net. The Differential Component Net is a pure fault component network, and its terminals’ voltages are zero. In the Differential Component Net, the voltage distribution from local terminal to fault point can be calculated by local terminal’s current. Considering the condition that the remote terminal voltage of Differential Component Net is zero, and using the voltage distribution of some point as excitation source, the infeed current from remote terminal can be calculated. In the condition that fault infeed from both terminal is given, the fault point can be found out according to the boundary condition of fault point. The accuracy and validity of the proposed method are verified by simulations.
What problem does this paper attempt to address?