A NOVEL TIME-DOMAIN ALGORITHM FOR LOCATING FAULTS ON PARALLEL TRANSMISSION LINES BY CIRCULATING CIRCUIT

宋国兵,索南加乐,许庆强,张健康
DOI: https://doi.org/10.3321/j.issn:0258-8013.2004.03.005
2004-01-01
Abstract:In fault states, parallel transmission lines can be uncoupled into Common Component Net and Differential Component Net. According to the fact that Differential Component Net is just constituted by parallel transmission lines part and its terminal-voltage is zero, voltage distribution along Differential Component Net can be calculated by terminal- current only. A new fault location algorithm is obtained by the principle that the least difference of voltage distribution computed by each terminal-current is exactly at the fault point. Because no voltage is involved in the proposed algorithm, there is no influence from CVT for which cannot transfer high frequency transient signal. From transient state to steady state, any segment of fault current can be used to locate faults by the algorithm. The algorithm needs an extreme short data window which is just a little longer than double propagation time of the parallel transmission lines. Using distributed parameter line model, the proposed algorithm is applicable for long distance lines since shunt capacitance is taken into account. Simulations show that, the locating error is less than 0.15km, and the fault types and fault resistances have no influence on locating precision.