Fault Location for Parallel Transmission Lines on the Same Tower Based on One-Terminal Current

宋国兵,索南加乐,许庆强,张健康
DOI: https://doi.org/10.3969/j.issn.1674-3415.2004.07.001
2004-01-01
Abstract:The method for fault location of the parallel transmission lines on the same tower based on single-terminal current is proposed in this paper. In the fault state, parallel transmission lines could be decomposed into same directional component nets and circumfluence component nets, of which the latter have no relation to systems outside the double-circuit lines and their voltage at two terminals are zero. According to the feature of parallel transmission lines′ circumfluence component nets, voltage profile along circumfluence component nets can be calculated by one-terminal current only. Because the travelling wave in parallel transmission line′s circumfluence component nets have strong reflection at two-terminal buses, and weak reflection at fault points, the fault location can be achieved by finding the strongest overlapped point of forward and backward travelling wave, if the moment when the first travelling wave arrived at measuring point can be regarded as the originating point. Simulations show that the proposed fault location method has a satisfactory precision and are free from the influence of transition resistance. This project is supported by National Natural Science Foundation of China (No.50377032).
What problem does this paper attempt to address?