Three-terminal Fault Location Method for Travelling Wave Removing Influence of Wave Velocity

CUI Hao,WANG Fenghua,MU Ka,ZHANG Jun,LIU Yadong
DOI: https://doi.org/10.3969/j.issn.1007-290X.2016.06.018
2016-01-01
Abstract:In order to improve veracity of travelling wave based fault location method for power transmission lines ,a kind of three‐terminal fault location algorithm removing influence of wave velocity is presented on the basis of analyzing distance‐measuring error caused for reason of uncertainty of wave velocity .Three travelling wave fault location devices with time synchronous modules are installed respectively at both terminals and any location in the middle segment of the line ,and grille fractal algorithm is applied to extract arrival time of initial travelling wave at the time of line fault .Based on proportional relationship of transmission distance and time of travelling wave ,fault location formula about time of fault initial travelling wave reaching to each measuring point is established .Both theoretical analysis and simulated results indicate that this method is not affected by transmission velocity of travelling wave and is able to effectively improve veracity of fault location of pow‐er transmission lines .
What problem does this paper attempt to address?