Dual-terminal Asynchronous Fault Location Algorithm for Long Transmission Line with Shunt Reactor in Middle

ZHANG Dequan,LUO Shenzeng,LI Yinhong
DOI: https://doi.org/10.16081/j.issn.1006-6047.2016.11.019
2016-01-01
Abstract:An asynchronous fault location algorithm based on the power-frequency measurements at two terminals is proposed for long transmission line with shunt reactor in middle.For the shunt reactor with fixed equivalent impedance,its equivalent impedance is estimated with the pre-fault phasors of two terminals and the fault is located based on post-fault positive-sequence network.For the controllable shunt reactor or that without pre-fault data,a fault location algorithm irrelative to the shunt reactor model is proposed,which exploits the characteristics of voltage and current phasors at fault point to construct the fault location function according to the boundary conditions of different fault types.Analysis shows that,the fault location function has monotonicity in the corresponding location sections,which means it can be quickly solved because there is no false root in a location section.The proposed algorithms are both based on the distributed-parameter line model and the asynchronous phasor of two terminal data is compensated by preor post-fault measurements.The simulative results based on PSCAD/EMTDC and MATLAB show that,the proposed algorithms are simple,accurate and suitable for different asynchronization angles,fault types,fault locations and transition resistances.
What problem does this paper attempt to address?