Abstract:RLC distributed line model-based fault location algorithm for EHV T-connection is presented. Its features are: (1) The measurements at the three terminals do not need to be synchronized, so real-time communication is not needed. Only off-line post-fault analysis is required. (2) It need not classify the faults for the T-connection constructed by single-and single-circuit lines or by single and double-circuit lines. (3) The technique is suitable for long line too. In principle, the accuracy of locating fault is virtually free from shunt capacitance, fault transient impedance, fault distance, load currents and source impedances. The digital simulation results show that this fault location technique is effective.