Fault Location Method for Distribution Network Based on Synchronous Measurement

Huidi Wu,Yong Li,Liwei Xie,Liang Hou,Xia Shao,Long Zhao,Yijia Cao
DOI: https://doi.org/10.1109/ciced56215.2022.9929066
2022-01-01
Abstract:Faults in the distribution network, especially single-phase grounding short circuit, do great harm to the distribution network. According to the fault characteristics of distribution network, a fault location method for distribution network based on synchronous measurement is proposed. By configuring micro phasor measurement unit (μPMU) on the line, the data of three-phase current is processed to form a high-dimensional matrix. The multidimensional scaling (MDS) reduces the dimensions to form a coordinate matrix. The local outlier factor (LOF) is detected to identify the fault line, and the fault location is realized. The principle of this method is simple, and the simulation results show that the application of various fault features reduces the error, which can accurately locate the fault section.
What problem does this paper attempt to address?