Single Phase Grounding Fault Location Based on Frequency Domain Characteristics of Fault Current

Jiang Bo,Shi Shenxing,Dong Xinzhou,Wang Bin
DOI: https://doi.org/10.1109/apap.2011.6180831
2011-01-01
Abstract:This paper studies the fault current frequency spectrum characteristics of single phase ground fault in ungrounded distribution networks, and the fault location method based on it. Firstly, it analyzes the production mechanism of 2nd major frequency component, and the relationship between the 2nd major frequency component and series resonance frequency of the faulted line. Secondly, from the perspectives of lumped-parameter circuit, the relationship between 2nd major frequency component and fault location is deduced. Simulation cases are used to confirm the relationship. Last, the impact of load and initial fault phase angle on the 2nd major frequency component are researched. Simulation research proves the feasibility of the fault detection and location method based on frequency domain characteristics.
What problem does this paper attempt to address?