Arc High Impedance Grounding Fault Detection for Resonant Grounding Distribution System Based on Directed Area in Characteristic Frequency Band

Bin Wang,Xin Cui,Xinzhou Dong,Kun Liu
DOI: https://doi.org/10.1109/pesgm51994.2024.10688465
2024-01-01
Abstract:Detecting high resistance grounding faults in distribution networks with neutral grounding via Peterson coils is challenging due to various factors, including the weak fault current magnitude, intermittent arc discharge behavior, and the uncertain tuning degree of Peterson coil. Current detection methods often overlook the dynamic fault development process, resulting in a lack of reliability and sensitivity. To address these issues, this paper presents an analysis of the dynamic trajectory of voltage-current characteristic curves based on zero sequence voltage and current within the characteristic frequency range. We introduce a straightforward and intuitive directed area method to extract the dynamic trajectory's direction, and propose an effective fault detection approach by combining initial polarity and the directed area information. The good performance of the proposed algorithm is validated through simulations and field test data.
What problem does this paper attempt to address?