Synchronous Measurement Based Transient High Resistance Earth Fault Location in Resonant Grounding System

Xiaoru CHEN,XUEYongduan,WANGChao,XUBingyin,HUANGRenle,CHENGLin
DOI: https://doi.org/10.7500/AEPS20160315016
2016-01-01
Abstract:High resistant earth fault occurs frequently in resonant grounding systems,and is difficult to detect.The existing transient analysis and transient faulty section location method is not suitable for high resistance earth fault.The unique role of parallel resonance between Peterson coil and system capacitance to ground is used.The variation laws of zero-sequence current, zero-sequence voltage and their transient components are analyzed in under-damping and over-damping resonant processes.The facts can be observed in this study that the transient currents of downstream fault points of detecting point are approximately orthogonal to the transient zero-sequence voltage,and the transient currents of upstream fault points of detecting point include transient current at the fault point proportional to the magnitude of the transient voltage.The fault information collected by the synchronous measurement unit is used to calculate the proj ection components of transient current on transient voltage in every detecting point.If the difference in current proj ection magnitudes between two adj acent detecting points is larger than the preset number,this section could be located as the fault section.Otherwise,the downstream last detecting point is the fault section.The proposed method is intended to perfect the fault transient analysis and faulty section location technology in non-solidly earthed network.The feasibility of the method is verified by simulation.