Power Distribution Network Ground Fault Location Algorithm Using On-Line Detectors

吴振升,杨学昌,伊贵业
DOI: https://doi.org/10.3321/j.issn:0258-8013.2001.12.002
2000-01-01
Abstract:An on line monitoring method is proposed for locating line to ground faults in ungrounded distribution networks with offset lines. The method is developed for on line detectors installed in the main branch of the distribution network. The detector includes an optical zero sequence current transducer, a microprocessor system and communication instrument for using the digital power line method. The information from the zero sequence current detector is collected by the signal processing instrumentation in the transformer substation to quickly locate the grounded fault. The residual current produced by the imbalance among the three phase sensors is analyzed by residual signal reduction processing. An artificial grounds fault test confirmed that the detector can accurately locate faults in automated distribution systems.