Study on Single-Phase Grounding Current Protection of Distribution Line in Neutral Grounding System Via Arc Suppression Coil

Jingji Shi,Shenxing Shi,Xinzhou Dong
DOI: https://doi.org/10.1109/apap59666.2023.10348405
2023-01-01
Abstract:Malignant accidents caused by single-phase grounding of distribution lines in neutral grounding system via arc suppression coil occur from time to time, and reliable and selective protection technology is an effective response. The sudden change of phase current generated by single-phase grounding can detect single-phase grounding fault sensitively and reliably, but its duration is short, which can not meet the selective requirements. In this paper, the criterion of phase current mutation based on rolling algorithm is improved, and the supplementary criterion and time delay criterion for judging whether the fault still exists based on phase current mutation and then locking the zero-sequence current are proposed. The zero-sequence current variation proposed in the scheme can still correctly judge the fault under unbalanced load. In this paper, the simulation model of PSCAD single-phase grounding protection is developed, and the simulation results show that the proposed method can selectively and reliably protect single-phase grounding fault from the influence of distribution network unsymmetrical load.
What problem does this paper attempt to address?