LOCATION DETECTION FOR THE STATOR SINGLE-PHASE GROUND FAULT OF A GENERATOR
毕大强,王祥珩,李德佳,余高旺,王维俭
DOI: https://doi.org/10.3321/j.issn:1000-1026.2004.22.012
2004-01-01
Abstract:Fault location for ground fault of a generator can extend the present function of ground fault protection and help the fast detection and clearance of the ground fault. This paper proposes a method to detect the location of stator ground fault for a generator, whose neutral is grounded via the distribution transformer with a parallel resistance at secondary winding. After the zero-sequence fundamental voltage enables the function of fault localization, the fault phase is determined according to the characteristic, that the terminal voltage of fault phase is the lowest. Furthermore, in terms of the relationship among the fault location, zero-sequence fundamental voltage, fault phase voltage, winding capacitance to ground and grounding transient resistance, which is obtained by the injection 20 Hz voltage protection, the fault location is calculated. The proposed method of fault localization is simple and practicable, and does not need additional equipment. The experimental results demonstrate that the method is correct and valid.