Analysis and calculation of the neutral point earthing mode selection for generators

Shen Jie
Abstract:The generator's neutral point earthing modes in Baosteel Power Plant Unit 4 was analyzed.The ordinary method to determine the neutral point earthing resistor value was not adopted.Three factors should be considered when selecting neutral point earthing resistance: limiting the generator's earthing fault current,restraining transient over-voltage and preventing the effect of zero sequence over-voltage on relay protection by the HV side grounding fault.A simplified calculation method for choosing neutral point earthing devices was obtained,the engineering calculation of the neutral point earthing resistance and transformer value was made and the equipment selection was optimized.