Simplified Calculation of Grounding Resistance of Substation Grounding System in the Two-layer Soil
LI Zeng,WU Guang-ning,FU Long-hai,REN Xiao-na,CAO Xiao-bin
DOI: https://doi.org/10.13336/j.1003-6520.hve.2008.01.029
2008-01-01
Abstract:To calculate the grounding resistance of the grounding grid in the two-layer soil, a simplification method for a two-layer soil structure is proposed. The influences of grounding area, the shape of the grounding grid, top-layer soil resistivity, top-layer soil thickness and the reflective coefficient on the equivalent soil resistivity are analyzed. The results show that grounding area, top-layer soil resistivity, top-layer soil thickness and the reflective coefficient are the key parameters that influence the equivalent soil resistivity. The top-layer soil resistivity has a linear relationship with the equivalent soil resistivity, so the grounding area, top-layer soil thickness and the reflective coefficient are chosen to simplify the analysis. The grounding area, top-layer soil thickness and the reflective coefficient have nonlinear relationships with the equivalent soil resistivity. It is hard to describe the relationship by the conventional mathematic function, while the BP artificial neural network can describe the nonlinear relationship exactly. According to the data calculated by the CDEGS software, the system model of BP ANN to calculate the equivalent soil resistivity is discussed. Compared with the actual calculation results, the errors of grounding resistance is controlled within a reasonable range, this system model is reliable. This method is helpful to the design of the grounding system in the multilayer soil.