Study of Influence Factors of Dual-layered Soil on Vertical Grounding Rod Performance
LI Sheng-lin,WU Guang-ning,CAO Xiao-bin,ZHOU Wei-ming,LI Rui-fang,FAN Chun-lei,S LI,X CAO,W ZHOU,R LI,C FAN
DOI: https://doi.org/10.3969/j.issn.1003-8337.2007.05.011
2007-01-01
Abstract:At substation having high soil resistivity and small site area the grounding resistance only horizontal grounding grid can not meet the requirement of relevant regulations for grounding resistance,and resistance-reduction measure is needed.Using CDEGS program,the author analyzed the influence of variation conserning resistivity of upper soil layer,reflection factor,thickeness of upper soil layer and length of vertical grounding rods on resistance reduction rate.The result shows that different resistivity of upper layer effects a little the resistance reduction rate which drops as the reflection rate lists,very small effect of reflection factor formed on resistivity reduction the resistance reduction,rate increases as the length of vertical grounding rod increases,tending to saturation in certain rising extent.The vertical grounding rod planting in lower soil layer can considerally reduce the grounding resistance when the reflection factor is negative.