Effectivity of Slanting Grounding Electrode on Improving Grounding Grid Performance

ZHANG Bo,ZENG Rong,HE Jin-liang
DOI: https://doi.org/10.3969/j.issn.1673-7598.2008.03.002
2008-01-01
Abstract:The effectivity and merit of slanting grounding electrode on improving grounding grid performance are analyzed in this paper by comparing the effect of all kinds of grounding electrode.The conclusions are verified by practical project.The slanting grounding electrode has the merits of both deep vertical grounding electrode and area enlargement without land expropriation. Comparing with the vertical grounding electrode,the shielding effect among the slanting grounding electrodes is also very small.Thus, for the grounding grid in uniform soil,using the slanting grounding electrode to reduce ground resistance is more effective than using the vertical grounding electrode with same length.When the resistivity of deep layer soil is higher than that of surface layer soil,the effect of equalizing voltage and reducing resistance by the slanting grounding electrode will be better.
What problem does this paper attempt to address?