Research on improving DC current distribution in earth by interconnecting DC grounding electrodes

Yilong Huang,Jianbao Guo,Bo Zhang,Fangyuan Cao
DOI: https://doi.org/10.13335/j.1000-3673.pst.2016.1682
2017-01-01
Abstract:DC current in DC grounding electrode can result in transformer DC bias in AC power grids and underground pipeline erosion nearby,becoming a main problem in DC grounding electrode construction and DC system operation.Interconnecting existing nearby grounding electrode is one of measures to reduce DC grounding current influence.This paper takes four DC grounding electrodes in China Southern Power Grid in Guangdong as example.By taking account of current field in soil due to DC grounding electrodes and circuit of connection network above ground,a coupled field-circuit model is set up.Then,with help of numerical simulation,method interconnecting grounding electrodes is studied according to grounding current distribution,ground potential rise,and so on.A scheme is put forward collecting all grounding currents to a busbar and redistributing them to grounding electrodes.The current assigned to each grounding electrode can be optimized by choosing suitable connecting conductors to adjust connecting resistance.Comparative analysis shows that the proposed scheme can greatly reduce influence of DC current on transformer in AC power grid,buried pipelines and other facilities.Future new DC project can connect to group of existing grounding electrodes directly without building new electrode.The scheme is reliable,flexible,easy to expand,and has a high price ratio.