Grounding Drainage Measures to Reduce Influence of DC Grounding Electrode on Pipeline

Yongli LIAO,Fangyuan CAO,Xiaobo MENG,Ruihai LI,Bo ZHANG
DOI: https://doi.org/10.13648/j.cnki.issn1674-0629.2017.09.002
2017-01-01
Abstract:With the rapid growth of energy demand in China, more and more DC transmission projects are adjacent to buried oil-gas pipeline, which leads to serious electromagnetic effects on buried metal pipeline.Focusing on the protection measures of pipeline, this paper establishes a circuit model based on the study of concentrated grounding device, sacrificial anode, forced cathode drainage meas-ures.Protective effect and regularities of these measures have been studied by simulation.Results show that concentrated grounding device of pipeline can reduce pipe-ground voltage of partial pipeline significantly, but its range of action is too small.Sacrificial anode has a palpable effect of reducing pipe-ground voltage as long distance buried pipeline.What's more, multipoint connection between sacrificial anode and pipe can obtain a better protection effect.The forced current cathodic drainage protection can also reduce the pipe-ground voltage.
What problem does this paper attempt to address?