Influence of Common Grounding Electrode on Yunnan-Guangdong DC Transmission Project and Guizhou-Guangdong Ⅱ DC Transmission Project

CHEN Fan,HE Jin-liang,ZHANG Bo,CAO Lin,ZHAO Jie,L(U) Jinz-huang
DOI: https://doi.org/10.13336/j.1003-6520.hve.2009.04.006
2009-01-01
Abstract:A common grounding electrode will be shared by Yunnan-Guangdong ultra high voltage DC transmission project and Guizhou-Guangdong Ⅱ DC transmission project to save construction area and cost. We created a PSCAD/EMTDC model of two HVDC systems sharing a common grounding electrode. Several typical situations including operation and fault conditions were simulated using the model. The rises of neutral point current of transformers in converting plants of two HVDC systems caused by ground return mode of HVDC system were also analyzed. Simulation results show the influences of common grounding electrode on the system overvoltage level, control system and protection system are extremely small.
What problem does this paper attempt to address?